AWG wire

Wire gauge size, resistance, current guide and voltage drop.

Diameter–
Cross-section
–
Resistance (20 °C)
–
Chassis wiring, single wire in air
–
Building wire (NEC 60 / 75 / 90 °C)
–
Breaker limit (NEC 240.4(D))
–
Voltage drop
–
Drop as % of supply
–
Power lost in the cable
–

How it works

AWG diameter: d = 0.005 in × 92(36 − n)/39. Copper resistance: 17.24 Ω per km for 1 mm² at 20 °C. The voltage drop counts both wires (there and back).

Current ratings depend on insulation, temperature, bundling and local rules. The chassis figures are a common guide for a single wire in free air; building-wire figures are from NEC table 310.16 (copper, up to three conductors). Keep the drop under 3–5 %.